Commonwealth Consolidated Regulations(regulation 129)
Method I
Bulkheads within main vertical zones
2. A B class division referred to in the last preceding item shall be constructed of, but, subject to item 12 of this Method, need not necessarily be faced with, incombustible material.
3. All doorways and similar openings in a bulkhead shall provide resistance to fire and have a method of closure consistent with the type of bulkhead in which they are situated.
4. The bulkheads in an accommodation space or service space shall be joined together in a manner which ensures the maximum resistance to fire.
5. A bulkhead in an accommodation space or service space shall extend from deck to deck or, except in the case of a corridor bulkhead, from the deck to a ceiling consisting of incombustible material.
6. Where the shell plating of the ship forms the boundary of an accommodation space or service space, the transverse bulkheads adjacent to the shell plating shall extend to the shell plating or, except in the case of a corridor bulkhead, to a lining consisting of incombustible material.
7. Where the external plating of a deckhouse in the ship forms the boundary of an accommodation space or service space, the transverse or longitudinal bulkheads adjacent to the plating shall extend to the plating or, except in the case of a corridor bulkhead, to a lining consisting of incombustible material.
8 A ventilation opening in a door in a B class division:
Automatic fire alarm and fire detection systems
Use of combustible and incombustible material
11. The facings, mouldings, decorations and veneers installed in an accommodation space or service space consisting of a corridor or stairway enclosure shall consist of incombustible materials.
12. The total volume of combustible materials installed as facings, mouldings, decorations or veneers in an accommodation space or public space, except a corridor or stairway enclosure, shall not exceed a volume equal to that of a veneer of one-tenth of an inch on the combined area of the walls and ceiling of the space.
Method II
Automatic sprinkler, fire alarm and fire detection system
2. The system shall be:
Pressure tank
5. The pressure tank shall be fitted with an efficient relief valve and with a water-gauge glass and a pressure gauge.
6. Stop valves or cocks shall be provided at each of the gauge connexions.
Air compressor
Pipes
External connexions
12. Shut-off valves for the shore supply and the ship's fire-main connexion shall be clearly and permanently marked to show their purpose and shall be capable of being locked in the closed position.
Pumps
14. The pump shall be so connected to the system that the pump is brought into action automatically by a pressure drop in the system before the standing fresh-water charge in the pressure tank is completely exhausted.
15. The pump shall have a suction direct from the sea and independent of any other suction.
16. There shall be fitted close to the pump on the delivery side a waste valve having an effective discharge area at least equivalent to the total discharge area of fifteen sprinklers, with a short open-ended discharge pipe for testing purposes.
17. The pump shall be capable of maintaining the rated sprinkler operating pressure at the level of the highest sprinkler with the waste valve referred to in the last preceding item fully open.
18. The system shall be so arranged that the pump cannot pass sea water into the pressure tank.
Sprinkler heads
20. A section of sprinkler heads:
22. A control valve shall be so constructed as to be capable of being operated only by means of a key or special tool which does not form part of the valve.
23. A pressure gauge shall be provided at each control valve and at a central station to indicate the pressure of water available throughout the system.
24. The sprinkler heads shall be capable of operating with salt water.
25. The temperature at which sprinkler heads come into operation shall be not less than one hundred and fifty-five degrees Fahrenheit and, except in the case of sprinkler heads in drying rooms and similar spaces, shall be not more than 212 degrees Fahrenheit.
26. A sprinkler head shall be capable of discharging water at a rate of not less than twenty gallons per minute under a supply pressure of twenty-five pounds per square inch.
27. The placing of sprinkler heads shall be such that:
29. The sprinkler system shall include means for giving a visible and audible alarm signal automatically whenever any sprinkler comes into operation.
30. The alarm signal shall indicate at one or more points in the ship, so as to come rapidly to the attention of the master and crew of the ship, the presence and position of any fire in the spaces served by the system.
31. If the alarm is operated by electricity, it shall be constructed so as to operate if any derangement occurs in the electrical circuit.
32. Not less than two sources of power, one of which shall be anemergency source of power, shall be provided to operate the independent pump, air compressor and automatic alarm.
Provisions for testing
34. Means shall be provided for testing the automatic cutting in of the pump.
35. Switches shall be provided at one of the points referred to in item 30 of this Method so that the alarm and the indicators for each section of sprinklers may be tested.
36. In a passenger ship the superstructure of which is constructed from a material other than steel, the whole unit, including the sprinkler pump, tank and air compressor shall be situated in an approved position remote from the boiler and machinery spaces.
METHOD III
Bulkheads within main vertical zones
2. All doorways and similar openings in a bulkhead shall provide resistance to fire and have a method of closure consistent with the type of bulkhead in which they are situated.
3. The bulkheads in an accommodation space or service space shall extend from deck to deck and shall be joined together so as to form a continuous network of B class divisions or of A class divisions and B class divisions, as the case may be.
4. The area of a compartment formed by the network of bulkheads referred to in the last preceding item:
6. The insulation of A class divisions and B class divisions, except those constituting the separation of the main vertical zones, the control stations, the stairway enclosures, and the corridors, may be omitted when the divisions constitute the outside part of the ship or when the adjoining compartment does not contain fire hazard.
7. A corridor bulkhead in an accommodation space or service space, if it is not a bulkhead which is required by these Regulations to consist of A class divisions, shall consist of B class divisions which shall extend from deck to deck and, if ceilings are fitted, the ceilings shall be of incombustible material.
8. All other partition bulkheads shall extend from deck to deck vertically and to the shell or other boundaries transversely except where incombustible ceilings or linings are fitted in which case the bulkhead may terminate at the ceiling or lining.
9. A ventilation opening may be installed in the lower portion of a door in a B class division.
10. B class divisions other than those required to be of the incombustible type, shall have an incombustible core and shall be assembled with internal layers of sheet asbestos or other approved material.
Automatic fire alarm and fire detection systems
Use of combustible and incombustible material
13. The grounds and supports for the linings and ceilings in a public room shall be constructed of steel or other equivalent material.