23A—Work in proximity to exposed conductors etc

        (1)         Work must not be carried out in proximity to exposed conductors or exposed parts of electrical equipment unless—

            (a)         it is carried out—

                  (i)         by a person who is suitably trained and qualified for such work beyond the approach limits set out in this regulation for such persons; or

                  (ii)         by a person who has been instructed in the identification of high and low voltage overhead conductors and the safety aspects of work near live powerlines beyond the approach limits set out in this regulation for such persons; and

            (b)         it is carried out beyond the approach limits set out in this regulation that are applicable in the circumstances.

        (2)         However, a person may work within the approach limits if—

            (a)         the work can be carried out safely in any of the following circumstances:

                  (i)         there are installed suitable barriers or earthed metal shields between the person carrying out the work and the conductors or electrical equipment;

                  (ii)         the work to be carried out is testing of equipment and the equipment is designed such that the approach limits cannot be complied with;

                  (iii)         the work to be carried out is earthing of the conductors or equipment and is carried out after the exposed conductors have been isolated and proved to be de-energised; and

            (b)         written instructions have been given, either generally or in a particular case, about the work and the precautions to be taken.

        (3)         For the purposes of this regulation, the approach limits for a person, including an article of clothing worn by a person, or a conductive object held or carried by the person, are set out below—


Voltage of conductor or equipment

Approach limit A

Approach limit B

Approach limit C
(i)          (ii)


(Distance in metres)

Not more than 1000V

0

0.3

3.0

1.0

More than 1000V but not more than 11kV

0.3

0.6

3.0

2.0

More than 11kV but not more than 33kV

0.45

0.9

3.0

3.0

66kV

0.7

1.4

4.0

4.0

132kV

1.2

2.4

5.0

5.0

275kV

2.0

4.0

6.0

6.0

where—

            (a)         approach limit A applies to a person suitably qualified and trained to work in proximity to exposed high and low voltage conductors or exposed parts of high and low voltage electrical equipment;

            (b)         approach limit B applies to a person who has been instructed in the identification of high and low voltage overhead conductors and the safety aspects of work near live powerlines;

            (c)         approach limit C(i) applies to a person using power operated tools;

            (d)         approach limit C(ii) applies to a person using manually operated tools.